Recovering Wastewater in a Cooling Water System with Thermal Membrane Distillation
摘要:A cooling water system is widely used in industry, where cooling towers consume large amounts of fresh water each year. In this study, to reduce fresh water consumption of the system, thermal membrane distillation (TMD) is used to treat blowdown water of the cooling tower, and permeate water is sent back to the tower as makeup water. TMD is driven by waste heat of the process stream which is initially cooled by the cooling water system. To obtain the optimal framework with minimum cost, the design and operation of cooling towers and TMD are optimized simultaneously. A case study taken from industry is employed to express the effectiveness of the proposed model. Results show that the optimization model can obtain up to 29.4% reduction on fresh water consumption in comparison with the system without wastewater recovery. Results also indicate that when the water price is higher than 1.067$/ton, the structure with the TMD unit is profitable.
© 2018 American Chemical Society.
ISSN号:0888-5885
卷、期、页:v 57,n 31,p10491-10499
发表日期:2018-08-08
期刊分区(SCI为中科院分区):二区
收录情况:EI(工程索引)
发表期刊名称:Industrial and Engineering Chemistry Research
参与作者:冯霄,徐冬梅
通讯作者:马嘉泽,伊尔凡
第一作者:王彧斐
论文类型:期刊论文
论文概要:马嘉泽,伊尔凡,王彧斐,冯霄,徐冬梅,Recovering Wastewater in a Cooling Water System with Thermal Membrane Distillation,Industrial and Engineering Chemistry Research,2018,v 57,n 31,p10491-10499
论文题目:Recovering Wastewater in a Cooling Water System with Thermal Membrane Distillation